Description
Input: 0 to 10V; iin max = 500 µA
Output: 4 to 20mA, on load ≤ 500 Ω
Accuracy: better than 0.2%
Regulation: < 10-4, with load varying from 0 to 500 Ω
Ripple: < 150 μA
Response time: < 3 ms (can be increased upon request)
Isolation: triple, with input/output, input/supply and output/supply: 3kV~
Power supply voltage:
- standard, 24V DC ± 5% / < 25mA / 500Ω loaded and < 15mA unloaded
- optional power supply:
- 24V~ or 110V~ or 230V~ ±10% / 48Hz to 400Hz
- 5V or 12V or 48V DC
Possible load: 0 to maximum 500 Ω
Protections:
- against inverted connections on the input and power supply
- against accidental overvoltage on input: 2V
- against overloads and short-circuits
- against bipolar overvoltages on the output
- isolations 3000V~
- against vibrations, and tropicalisation: with moulding
- sealing iP67, except connections
- elimination of the faulty-contact risk (no DIL switch)
- negligible temperature rise (high performance conversion)
- electromagnetic compatibility CEM 89 / 336 / CE
Temperatures:
- coefficient: < 2.10-4 / °C
- operation: -20°C to +60°C
- storage: – 40°C to + 90°C
Three modules:
- DIN rail mounting (RD)
- wall mounting with external connector and 2 M3 screws (P)
- mounting on printed circuit, connecting pins ∅ 1mm (CI)
Optional: all-aluminum case, 89 x 35 x thickness 16 or 30mm, with three mounting possibilities (M)
For more information about this 0 to 0.5 V → 4 to 20 mA isolated converter: PDF