Description
Input:
- applied signal: 1.2V to 30V (accidental maximum: 50V)
- absorbed current: < 2 mA for Vin ≤ 5V / < 4 mA for Vin ≤ 10V / < 8 mA for Vin ≤ 30V
Output:
- output signal: 1.2V to 30V
- short-circuits: permitted
- load: ≥ 47 kΩ
Full-scale accuracy: better than 0.2%
Response time: < 5 ms (possible betterment, linearly, with an external capacitor)
Isolation: > 2000 V
Protections:
- against accidental overvoltage on input: up to 50V
- against overloads and short-circuits on output
- isolation: 3000V
- increased reliability because of no external power supply
- against vibrations; tropicalisation with moulding
- sealing iP67, except connections
- elimination of the faulty-contact risk (no DIL switch)
- negligible temperature rise (high performance conversion)
- electromagnetic compatibility CEM 89 / 336 / CE
Temperatures:
- coefficient: < 2.10-4 / °C
- operation: -20°C to +60°C
- storage: – 40°C to + 90°C
Three modules:
- DIN rail mounting (RD)
- wall mounting
- mounting on printed circuit
Upon request, with the same “self-powered” technology: choice of input range (example: 2V to 7V) for output 0 to 10V.
For more information about this 1.25 to 30V  → 1.25 to 30V voltage transmitter (isolated converter): PDF